CONFIGURING
THE METER
Read this section for step-by-step procedures on configuring your meter.
For a summary of menu configurations, refer to Table 6-1. Some menu items
do not display if your meter does not have analog output or dual relay
output capabilities. These menu items are noted accordingly in the following
sub- sections. Factory defaults are in bold and italics.
SELECTING
THE INPUT TYPE ("INPT")
To select your appropriate input type signal, follow
these steps:
1. Press the MENU button. The meter shows "INPT".
2. Press the /MIN
button. The meter flashes one of the following (default is 4004):
* "4004" = 44004
* "4005" = 44005
* "4006" = 44006
* "4007" = 44007
* "4008" = 44008
* "4016" = 44016
* "4018" = 44018
* "700" = Linear 3-Wire
3. Press the /MAX
button to scroll through available choices.
4. Press the MENU button to store your selection. The meter
momentarily shows "STRD", followed by "DEC.P" (Decimal Point).
SELECTING
A DECIMAL POINT POSITION ("DEC.P")
To select a decimal
point display position.
1.
Press the MENU button until the meter shows "DEC.P"
2. Press the /MIN
button. The meter shows one of the following:
* FFFF.
(default)
* FFF.F
* FF.FF
3. Press the
/MAX button
to scroll between available choices.
4. Press the MENU button to store your choice. The meter
momentarily shows "STRD", followed by the next menu "RD.C.F"
(Reading Configuration).
NOTE: When you change the decimal position the meter adjusts
setpoint values and setpoint deadbands. These adjustments are made according
to the new decimal point. If one or more of these values overflow, the
meter flashes "ER2" when you store new decimal point position value.
USING READING CONFIGURATION
("RD.CF")
To select if the meter shows in Fahrenheit or Celsius, follow these steps:
1.
Press the MENU button until "RD.CF" displays.
2. Press the /MIN
button. The meter shows one of the following:
* "R.1=F" Fahrenheit - Default
* "R.1=C" Celsius
3. Press the /MAX
button to toggle between available selections.
4. Press the MENU button to store your choice. The meter
momentarily shows "STRD", followed by "S1.CF" (Setpoint 1 Configuration)
USING
SETPOINT 1 CONFIGURATION ("S1.CF")
Setpoint 1 Configurations display only if your meter has dual relay
output capabilities. You may use Setpoint 1 Configuration ("S1.CF")
for the following:
* To set setpoint
1's active band above or below your chosen value
* To select whether setpoint 1's operation is latched or unlatched
Setting
Setpoint 1's Active Band
1.
Press the MENU button until the meter shows "S1.CF".
2. Press the /MIN
button. The meter shows one of the following:
*"S.1=A"
(Active above the deadband) (default)
* "S.1=B" (Active below the deadband)
3. Press the
//MAX button
to toggle between available choices.
4. Press the /MIN
button to select if Setpoint 1 is latched or unlatched or press the MENU
button to store your selection and enter "S2.CF" (Setpoint 2 Configuration)
Selecting if Setpoint 1 is
Latched or Unlatched
1. Press the /MIN
button. The meter shows one of the following:
* "S.2=L"
(setpoint 1 to be latched) (default)
* "S.2=U" (setpoint 1 to be unlatched)
2. Press the
//MAX button
to toggle between available choices.
3.
Press the MENU button to store your choice(s). The meter momentarily
shows "STRD", followed by "S2.CF" (Setpoint 2 Configuration).
USING SETPOINT 2 CONFIGURATION
("S2.CF")
Setpoint 2 Configurations display only if your meter has dual relay
output capabilities. You may use Setpoint 2 Configuration ("S2.CF")
for the following:
* To set setpoint's
2's active band above or below your chosen value
* To select whether the setpoint 2's operation is latched or
unlatched
Setting
Setpoint 2's Active Band
1. Press the MENU button until the meter shows "S2.CF".
2.
Press the /MIN
button. The meter shows one of the following:
* "S.1=A" (Active above the deadband) (default)
* "S.1=B" (Active below the deadband)
3. Press the //MAX
button to toggle between available choices.
4. Press the /MIN
button to select if setpoint 1 is latched or unlatched or press the MENU
button to store your selection and enter "S1.DB" (Setpoint
1 Deadband).
Selecting if Setpoint 2 is
Latched or Unlatched
1. Press the /MIN
button. The meter shows one of the following:
* "S.2=L" setpoint 1 to be latche - default
* "S.2=U" setpoint 1 to be unlatched
2. Press the /MAX
button to toggle between available choices.
3. Press the MENU button to store your selection(s). The meter
momentarily shows "STRD", followed by "S1.DB" (Setpoint 1 Deadband).
SETTING THE SETPOINT 1 DEADBAND
("S1.DB")
Setpoint 1 Deadband displays only if your meter has dual relay output
capabilities. Factory default deadband is 003. To change the deadband
(hysteresis) of setpoint 1, follow these steps:
1. Press the MENU button until the meter shows "S1.DB".
2. Press the /MIN
button. The meter shows the last previously stored 4-digit number (0000
through 9999) with flashing 4th digit.
3. Press the /MAX
button to change the value of the flashing digit. If you continue to press
the /MAX
button, the flashing digit's value continues to change.
4. Press the /MIN
button to scroll horizontally to the next digit.
5. Press the MENU button to store your selection. The meter
momentarily shows "STRD", followed by "S2.DB" (Setpoint
2 Deadband).
SETTING
THE SETPOINT 2 DEADBAND ("S2.DB")
Setpoint 2 Deadband displays only if your meter has dual relay output
capabilities. Factory default deadband is 003. To change the deadband
(hysteresis) of setpoint 2, follow these steps:
1. Press the MENU button until
the meter shows "S2.DB".
2. Press the /MIN
button. The meter shows the last stored number (0000 through 9999) with
flashing 4th digit.
3. Press the /MAX
button to change the value of the flashing digit. If you continue to press
the /MAX
button, the flashing digit's value continues to change.
4. Press the /MIN
button to scroll
to the next digit.
5. Press the MENU button to store your selection. The meter
momentarily shows "STRD" , followed by "OT.CF" (Output Configuration).
USING OUTPUT CONFIGURATION ("OT.CF")
Output Configuration displays only if your meter has analog output
capabilities. Use Output Configuration ("OT.CF") to select
the following:
* To enable or disable the analog output
* To determine if the analog output is current or voltage
Enabling or Disabling the Analog Output
To enable or disable the analog output.
1. Press the MENU button until the meter shows "OT.CF".
2. Press the /MIN
button.
The meter shows one of the following:
* "O.1=D" Analog output disabled
* "O.1=E" Analog output enabled - default
3. Press the /MAX
button to toggle between available choices.
4. Press the /MIN
button to select analog output as current/voltage or press the
MENU button to store your selection (the meter momentarily shows
"STRD", followed by "OT.S.O", Output Scale and Offset -
refer to Section 4.11)..
SELECTING
ANALOG OUTPUT as CURRENT or VOLTAGE
Remember that Output Configuration displays only if your meter
has analog output capabilities.
1. Press the /MIN
button. The meter shows one of the following:
* "O.2=V" Analog output = voltage
* "O.2=C" Analog output = current - default
2. Press the /MAX
button to toggle between available choices.
3. Press the /MIN
button to go back to selecting analog output as enabled or disabled or
press the MENU button to store your choices (the meter momentarily
shows "STRD", followed by "OT.S.O", Output Scale and Offset).
|